Crestron CHV-TSTATEX Guida di Installazione Pagina 51

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 92
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 50
Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
45
SETUP: OTHER SETTINGS
SETUP: OTHER SETTINGS
NO APPLICABLE SETTINGS
Press To Continue
No applicable settings.
SETUP: SENSORS
SETUP: SENSORS
SENSOR
INTERNAL:
REMOTE 1:
REMOTE 2:
>TEMP HUM
USE OMIT
SLAB
DETECTED: 1 x T
Press To Continue
INTERNAL: Choose USE or OMIT. Choose USE to permit
temperature averaging.
NOTE: Sensor temperature and humidity can be output to
network even if OMIT is chosen.
REMOTE 1 and 2: Choose USE, OMIT, OD (outdoors), or
SLAB (remote sensors only).
NOTE: REMOTE 1 and REMOTE 2 options do not appear
on this screen if these sensors are not connected.
NOTE: Thermostat auto-detects connected remote sensors.
SETUP: HUMIDITY SENSORS
SETUP: H-SENSORS
TRIM
INTERNAL: -5
REMOTE 1: 0
REMOTE 2: 0
% RH
45
50
30
Press To Continue
TRIM (-9+9) Allows the user to calibrate the INTERNAL,
REMOTE 1 and REMOTE 2 humidity sensors to match %
RH values obtained by other equipment. The values here are
based on a logarithmic index and are not to be interpreted as
units of measurement.
NOTE: For best results, calibration should be performed
when RH is 40% or higher.
Vedere la pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 91 92

Commenti su questo manuale

Nessun commento