SECTION 260933
(previously 16575)
Central Lighting and Dimming Controls
PART 1 - GENERAL
1.1 SUMMARY:
A. Work Included: The work of this Section shall cover all labor, materials, and
equipment to furnish Central Dimming Controls herein specified, including:
1. Lighting Controllers with Integrated Dimmers & Switches
2. Lighting Control System Processors
3. Lighting Control System User Interfaces
a. Keypads
b. Touch Panels
c. Web Based Interfaces
4. Lighting Control System Software
5. Lighting Control Communications Network
B. Complete System: The Contractor shall provide all items necessary for a complete,
safe, fully functional system as described herein including all tools, labor and
supervision, even though they may not be specifically enumerated.
1. Any errors, omissions or ambiguities do not relieve the Contractor of this
responsibility, but shall be brought to the attention of the Engineer for
clarification.
2. The Contractor shall be responsible for acquiring, installing, wiring and
coordination of all components and equipment.
3. The Contractor shall furnish all conduit, wire, connectors, hardware and other
materials necessary for a complete and properly functional lighting control and
dimming system as specified.
C. Related Sections:
1. Section [122000 - Window Treatments:] Window treatments controlled by the
Lighting Control System.
2. Section [260923 – Lighting Control Devices:] Occupancy and Daylight sensors
used in conjunction with the Lighting Control System.
3. Section [260926 – Lighting Control PanelBoards:] Lighting panels (switching)
controlled by the Lighting Control System.
4. Section [262726 - Wiring Devices]
5. Section [265113 – Interior Lighting Fixtures, Lamps, and Ballasts:] Fluorescent
lighting ballasts controlled by Lighting Control System.
1.2 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Contractor shall maintain accurate, as-built Panel Schedules detailing connection
and type of lighting loads in the system.
a. Schedules shall detail, at a minimum:
1) Circuit ID, Number, Or Designation.
2) Actual Connected Load, Voltage, And Load Type Per Circuit.
3) Clear Designation Of Emergency Loads, Where Applicable.
4) Circuits And Their Respective Control Zones.
b. Panel Schedules shall be indexed on a per panel per dimmer/ relay basis
c. Panel Schedules shall be updated and provided to the Manufacturer of the
Lighting Control System no later than (30) days prior to commissioning.
2. Contractor shall ensure that connected loads are compatible with the dimming
and switching equipment provided. These steps shall include:
a. Provision of manufacture of LED fixtures with associated drivers to the
Manufacturer of the Central Dimming Controls.
b. Provision of manufacture of Fluorescent fixtures with associated ballasts and
lamps to the manufacturer of the Central Dimming Controls.
Vedere la pagina 0
1 2 3 4 5 6 ... 10 11

Sommario

Pagina 1

SECTION 260933 (previously 16575) Central Lighting and Dimming Controls PART 1 - GENERAL 1.1 SUMMARY: A. Work Included: The work of this Sectio

Pagina 2

4) neon/ cold cathode 5) Advance Mark X Ballasts b. Dimming Control 120vAC to 277vAC: 3-Wire 20amp 120 to 277vAC Expansion Module, supporting up

Pagina 3

A. The Manufacturer shall provide the services of a qualified factory-employed field service engineer for a minimum of one (1) pre-wire visit and ins

Pagina 4

c. Provision of manufacture of Low-voltage fixtures including model number and type of transformer 1.3 SUBMITTAL REQUIREMENTS A. Submittals for Rev

Pagina 5

c. Contact information for 24 hour a day, 7 day a week, 365 day a year technical support hotline. 3. As-Built System Drawings, including: a. Shop d

Pagina 6

a. Evidence of compliance with Manufacturer Qualifications as outlined below. b. A listing of three (3) equivalent installations including: 1) Name

Pagina 7

4. Control Surfaces (preset controllers, touch panels and keypads) shall only be installed once the installation area is a “conditioned space”, as de

Pagina 8

1. Relay modules shall have eight separate channels or circuits that can be independently controlled through the Cresnet system. Each circuit shall

Pagina 9

2. Digital output: 250 mA sink from maximum 24VDC; catch diodes for use with “real world” loads. 3. Analog input: Rated for 0-10VDC, protected to

Pagina 10

A. General: The Integrated Multi-Zone Controller(s) shall have, at a minimum, the following features: 1. Integrated phase-forward dimming, switchin

Pagina 11

1. Connection to touch panels for custom interfaces, programming, preset recall, system state selection, and room combine/ partitioning functions. 2.